Paper
19 October 2022 Transformer winding temperature rise measurement system
Weili Wu, Hualong Zhang, Wentong Wu
Author Affiliations +
Proceedings Volume 12294, 7th International Symposium on Advances in Electrical, Electronics, and Computer Engineering; 122942J (2022) https://doi.org/10.1117/12.2640478
Event: 7th International Symposium on Advances in Electrical, Electronics and Computer Engineering (ISAEECE 2022), 2022, Xishuangbanna, China
Abstract
The temperature rise measurement of transformer winding is one of the main items of transformer factory and preventive test. Most of the existing transformer winding temperature rise measuring devices are designed and measured according to the thermal resistance method specified in the transformer test standard. However, due to the inherent properties of power transformer, it takes a long time to measure the DC resistance of the transformer winding. Considering the particularity of transformer DC resistance measurement, the value of transformer winding inductance is estimated, and the resistance is inserted in series in the measurement circuit to reduce the time constant of the circuit, so as to achieve the purpose of fast measurement. Based on this method, an automatic measurement system for temperature rise detection is developed and the temperature rise is accurately measured.
© (2022) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Weili Wu, Hualong Zhang, and Wentong Wu "Transformer winding temperature rise measurement system", Proc. SPIE 12294, 7th International Symposium on Advances in Electrical, Electronics, and Computer Engineering, 122942J (19 October 2022); https://doi.org/10.1117/12.2640478
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Transformers

Resistance

Temperature metrology

Inductance

Magnetism

Computing systems

Control systems

RELATED CONTENT